Laboratory taps and emergency equipment | Carlos Arboles
  * Minimum 3 characters.
Laboratory taps and emergency equipment | Carlos Arboles
Emergency showers and eyewashes - Showers and eyewash accessories

195120

Thermostatic valve 122 lpm at Δ2 bar


Print pdf
The valve delivers tepid water. In combination with our Emergency Showers and Eyewashes, it allows to fulfil with the recommendations about water temperature of the International Standards ANSI/ISEA Z358.1 and EN 15154.
 
SUPPLY CONDITIONS
CONNECTIONS: G1-1/4” M, with kit including two G1” M adapters with check valves on inlets.
HOT AND COLD WATER SUPPLY PRESSURE: Optimum 4 bar / Minimum 3.5 bar / Maximum 8 bar
HOT WATER SUPPLY TEMPERATURE: Optimum 50-70ºC (Maximum 100ºC)
COLD WATER SUPPLY TEMPERATURE: Optimum 5-10ºC (Maximum 23ºC)

PERFORMANCE
The valve mixes cold and hot water to deliver tepid water. Adjustable temperature, preset at 34ºC. Maximum flow of 122 lpm at Δ2 bar.
On failure of hot water supply, internal bypass delivers cold water to the Emergency Equipment. Minimum flow of 105 lpm at Δ2 bar.
On failure of cold water supply, hot water is shut down to prevent any damage to the user.




Amount:
Less
1
More










<<   Back